SKT Wood and Steel Post System – Tangent W-Beam Terminal
Yes, provided the distance from the exit slot of the terminal to the edge of the pavement for the oncoming traffic is at least 25 feet. Studies of many accidents have shown that a lateral distance of 20 feet was the effective maximum distance that any component of a damaged tangent terminal came to rest. The recommended 25-foot distance has a 5-foot safety factor. In addition, the proper Length-of-Need must be established.
No. The 6'-0" long steel foundation tubes without soil plates may only be used at SKT posts #1 and #2. If foundation tubes are used at SKT posts #3 and #4 or at #3 through #8, they must be the 4'-6" long foundation tubes. The soil plates for these short tubes at posts 3 through 8 are now optional. The 4'-6" long foundation tubes with soil plates may also be used at SKT post #1 and #2 if desired. Either way, steel foundation tubes must be used at posts #1 and #2 for the wood post option.
NO!! The SKT requires eight special 1/2" high-strength cable anchor bracket shoulder bolts with two structural washers and a 1/2" structural nut on the traffic side. The unthreaded shoulders of the bolts provide the release mechanism for the anchor bracket for end-on impacts.
Yes, but there are certain conditions that must exist. The adjoining downstream 25'-0" length of the system must utilize standard W6" x 8.5# (or 9#) x 6'-0" long guardrail posts. In addition, if the SKT-SP is joining with anything other than standard W-Beam rail (i.e. Thrie Beam or a transition), an additional 12'-6" of standard W6" x 8.5# (or 9#) x 6'-0" long guardrail posts must be used.
FLEAT Wood and Steel Post System – Flared W-Beam Terminal
When the FLEAT is attached to a run of guardrail that is parallel to the travelway, the offset flare for the FLEAT is measured from the point where the guardrail ends and the FLEAT begins. The offset for the Test Level 3 FLEAT can be varied anywhere between 2'-6" to 4'-0" (3.8 degrees to 6.1 degrees) over the 37'-6" long terminal length. The Test Level 2 FLEAT can be varied anywhere between 1'-8" to 2'-8" (3.8 degrees to 6.1 degrees) over the 25'-0" long terminal length. These offsets represent flare rates of 15:1 to approximately 10:1. When the FLEAT is attached to guardrail that has been flared per the recommendations of the AASHTO Roadside Design Guide, the flare rate for the FLEAT may not need to be changed from that of the downstream guardrail. If the flare rate of the guardrail falls between 15:1 and 10:1, install the FLEAT in line with the run of guardrail at the same flare rate. If the flare rate of the guardrail is less the 15:1, then you must adjust the FLEAT farther away from the run of guardrail to provide the proper flare rate. If the recommendations of the AASHTO Roadside Design Guide are followed, the standard run of guardrail will not have a flare rate that is greater than 10:1 (semi-rigid barriers) for Test Level 2 (70 km/hr) or Test Level 3 (100 km/hr) design speeds. This means the FLEAT should not need to be flared back toward the travelway with respect to the flare rate of the guardrail.
No. The contractor must install the FLEAT beginning at the downstream end where the run of guardrail begins and work toward post #1. The splice of the last FLEAT rail section where the flare departure begins (FLEAT post #7 for the 37'-6" long Test Level 3 system) must be firmly bolted before the rail within the FLEAT itself is flared. If desired, post #7 can be set back a short distance to minimize the severity of the bend at that post. The angle of departure will depend on the offset selected. Based on a Test Level 3 FLEAT that is 37'-6" long, the maximum angle will be 6.1 degrees for a 4'-0" offset and the minimum angle will be 3.8 degrees for a 2'-6" offset. For a Test Level 2 FLEAT, the angle will remain the same but the offset will change to 2'-8" and 1'-8" respectively.
No. The FLEAT only has steel foundation tubes at post #1 and #2. The tubes may either be the 6'-0" long steel foundation tubes without soil plates or the 4'-6" long foundation tubes with soil plates. Either way, steel foundation tubes must be used at posts #1 and #2 for the wood post option.
NO!! The FLEAT requires eight special 1/2" high-strength cable anchor bracket shoulder bolts with two structural washers and a 1/2" structural nut on the traffic side. The unthreaded shoulders of the bolts provide the release mechanism for the anchor bracket for end-on impacts.
Yes, but the adjoining downstream 25'-0" length of the system must utilize standard W6" x 8.5# (or 9#) x 6'-0" long guardrail posts.
SKT-MGS and FLEAT-MGS W-Beam Terminals for 31"-Tall Rail
Yes, but the offset caused by the blockouts in the terminal must be considered when driving the posts.
NO!! The SKT-MGS and FLEAT-MGS require eight special 1/2" high- strength cable anchor bracket shoulder bolts with two structural washers and a 1/2" structural nut on the traffic side. The unthreaded shoulders of the bolts provide the release mechanism for the anchor bracket for end-on impacts.
Yes, if the specifying agency has called for 8" blocks on the downstream MGS W-Beam Barrier, 8" blocks may be used in the terminals. Drawings are available upon request.
FLEAT-MT Wood or Steel Post – Median W-Beam Terminal
Yes, but consideration should be given to placement of the front 18'-9" single-sided segment. That portion of the terminal should be placed on the side where traffic volumes would be expected to be heaviest.
Yes. Drawings are available for this option.
NO!! The FLEAT-MT requires eight special 1/2" high-strength cable anchor bracket shoulder bolts with two structural washers and a 1/2" structural nut on the traffic side. The unthreaded shoulders of the bolts provide the release mechanism for the anchor bracket for end-on impacts.